Description
HPW02401.60T CAMTEC DIN-Rail Power Supply 85-264Vac 60Vdc/4A 240/312W 240W TS35mm IP20
HPW02401
- DIN-Rail Power Supply 1phase fix output TS35mm DIN EN 50022
- Active Inrush Current Protection
- Active PFC (Power Faktur Correktion)
- Remote Shutdown
- Temperature Control
- Clean C/V chart without foldback, ideal for dc drives and dc-UPS
HPW02401
Model | HPW02401 | |||||
Power | 240W/312W | |||||
Nominal AC Input | 100… 240Vac | |||||
Input Range AC | 90… 265Vac | |||||
Input Range DC | 120… 375Vdc | |||||
Input Frequency | 47… 63Hz | |||||
Hold-Up Time | 40ms | |||||
Inrush Current Protection | 5Aeff / 7Apeak electronic protection ±6% | |||||
Autostart | Soft start / Soft start 50ms | |||||
Output Voltage | 12V | 24V | 36V | 48V | 60V | 72V |
Adjust Range Vout | 9… 18V | 18… 30V | 30… 43V | 43… 53V | 53… 72V | 68… 86V |
Ripple & Noise mVpp | 30mV | 30mV | 60mV | 50mV | 50mV | 60mV |
Nominal Output Current 40°/60°C | 15/19A | 10/13A | 6,7/8,7A | 5/6,8A | 4.0/5.2A | 3,3/4,3A |
Power Boost <=60°C/60s | 18A | 12A | 8A | 6A | 5,,2A | 4,3A |
Stability at Load Switch | ±0,5% | ±0,2% | ±0,2% | ±0,2% | ±0,2% | ±0,2% |
Transient Time | < 1ms | |||||
Efficiency | 0,92 | |||||
Basic load | Idling-proof | |||||
Short Circuit Protection | Continuous | |||||
Ambient Operation Temperature | -20°C… +70°C | |||||
Cooling | Natural convection | |||||
Temperature Monitoring | yes | |||||
Dimensions (WxHxD) | 75x130x115mm | |||||
IP-Range | IP20 | |||||
Safety Norms | CSA UL CE according to IEC60950-1 | |||||
Safety IEC | EN60950-1 EN50178 EN60204-1 | |||||
Safety Class 1(A) | VDE0100 VDE0805 | |||||
Input to Output Isolation | 3000Vac | |||||
Climatic Class, Humidity | 3k3, 90% non condensing | |||||
EMI | EN55022B | |||||
EMS | EN61000-6-2,3 | |||||
MTBF IEC61709 | 500000h | |||||
Power Good Relay | Yes | |||||
Remote Shutdown | Yes | |||||
Features | Active PFC | |||||
Ordering options | Protective coating | |||||
Options | See datasheet |
Manufacturer:Camtec
Datasheet:camtec_hpw02401_e0714c.pdf