33802 Woehner NH Fuse Switch-Disconnector 690V 125A Busbar Mounted

33802 Woehner NH Fuse Switch-Disconnector 690V 125A, Connection bottom / top, size 000, Busbar Mounted, 3-pole RoHS

SKU: 33802 Category: Tag: Brand:

Description

33802 Woehner QUADRON 60 Classic NH fuse switch-disconnector size 000, 125 A, busbar mounted, connection bottom / top^box terminal with CrossLink Technology for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars only 49.5 mm wide rotatable for connection at bottom or top

for fuse links size: NH 000
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 9 W
Details IEC
Standards
IEC 60947-1:2007 + A1:2010 + A2:2014
IEC 60947-3:2008 + A1:2012 + A2:2015
GB/T 14048.3
Electrical data IEC
Rated current (IEC): 125 A
rated voltage (IEC) AC: 690 V
rated voltage (IEC) DC: 440 V
rated isolation voltage Ui AC: 800 V
rated isolation voltage Ui DC: 500 V
rated surge voltage Uimp : 6 kV

Utilisation category AC (IEC 60947-3) : AC-21B (690 V / 80 A)
AC-22B (400 V / 125 A)
cond. short-circuit current with fuses (AC): 50 kA / 690 V (80 A)
80 kA / 400 V (125 A)
100 kA / 400 V (100 A)
approved wth fuse links of operation class: gG

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 6.7 W.

(The power dissipation at full load would be 10.5 W.)
Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Whner for this conditions before designing your panel.
max. permitted voltage (IEC) DC: 800 V
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
for fuse links IEC 60269-2-1 / DIN VDE 0636-201 size 000 (max. 21mm wide)
In accordance with the specified AC and DC switching properties and in consideration of the overload conditions, certain distances to earthed metal parts are to be adhered to. detailed information upon inquiry

When several devices are used side-by-side in continuous operation, the rated load factor specified in IEC / EN 61439-1, Table 1, must be observed.
Mechanical data
W x H x D: 49.5 x 200 x 127
weight: 53.5 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
front degree of protection: IP30

type of fastening: patented click mechanism

Terminal points

box terminal:
1.5 – 50 mm2 flexible and flexible with wire-end ferrules*
2.5 – 50 mm2 flexible
2.5 – 16 mm2 solid round
2.5 – 50 mm2 stranded round

Terminal space 10 mm x 10 mm
Manufacturer:Electronic Components
Datasheet:woehner-33802000A.pdf

Product Enquiry