Integrated Power Designs REL-150-1006-CHCO Power Supply 24Vdc 6.3A

REL-150-1006-CHCO INTEGRATED POWER DESIGN POWER SUPPLY CHASSIS & COVER 24VDC 6.3A ITE & MEDICAL CERTIFICATION

Description

REL-150-1006-CHCO INTEGRATED POWER DESIGN POWER SUPPLY CHASSIS & COVER 24VDC 6.3A ITE & MEDICAL CERTIFICATION

RoHS?Compliant
Universal 85-264 VAC Input
High Efficiency
Advanced SMT Design
Compact 3.8” x 6.0” x 1.3” Size
2 Year Warranty
Fits 1U Applications

NPUT SPECIFICATIONS

Source Voltage
Frequency Range
Peak Inrush Current
Efficiency
Power Factor
85 – 264 Volts AC
47 – 63 Hz
40A
82% Typ., Full Power, 230V, varies by model
0.95 (Full Power, 230V)

OUTPUT SPECIFICATIONS

Total Output Power at 50°C

Output Voltage Centering

Output Voltage Adjust Range
Load Regulation V1
V2


V3
V4
Source Regulation
Cross Regulation
Output Noise
Turn on Overshoot
Transient Response
Voltage Deviation
Recovery Time
Load Change
Output Overvoltage Protection
Output Overpower Protection
Hold Up Time
Start Up Time
100W Convection Cooled
150W  300 LFM Forced Air Cooled
Output 1: ± 0.5% (All outputs at 50% load)
Output 2,3,4: ± 5.0%
Output 1: 95 – 105%
Output 1: 0.5% (10-100% load change)
Output 2: 5.0%
(4001-5) 8.0%
(2001) 6.0%
Output 3: 5.0%
Output 4: 5.0%
Outputs 1 – 4: 0.5%
Outputs 2 – 4: 5.0%
Outputs 1 – 4: 1.0%
None
Outputs 1 – 4
5.0%
500µS
50% to 100%
Output 1: 110% to 150%
110-160% rated Pout, cycle on/off, auto recovery
16 mS min., Full Power, 85V Input
5 Seconds, 120V Input

SAFETY & ELECTROMAGNETIC COMPATIBILITY SPECIFICATIONS

Safety Approvals


Electrostatic Discharge
Radiated Electromagnetic Field
EFT/Bursts
Surges
Conducted Immunity
Voltage Interruptions
Radiated Emissions
Conducted Emissions
Harmonic Current Emissions
Voltage Fluctuations & Flicker
Voltage Dips and Interruptions
EN 60950-1/A12:2011
EN 60601-1/A2:1995 , EN 60601-1:2006

EN 61000-4-2, ±8kV Contact Discharge ,   ±8kV Air Discharge
EN 61000-4-3, 80MHz-2.5GHz, 10/m, 80% AM
EN 61000-4-4, ±2 kV
EN 61000-4-5, ± 1 kV Common Mode ± 2 kV Differential Mode
EN 61000-4-6  .15 to 80MHz, 10V, 80% AM
EN 61000-4-11, 95% Reduction, 5s
EN 55011/22, Class B
EN 55011/22, Class B
EN 61000-3-2
EN 61000-3-3
EN 61000-4-11, 30% Reduction, 500ms
95% Reduction, 10ms

60% Reduction, 1s (Criteria B)
95% Reductions, 5000ms

ENVIRONMENTAL SPECIFICATIONS

Ambient Operating
Temperature Range
Ambient Storage Temp. Range
Temperature Coefficient
0° C to + 70° C
Derating: See Power Rating Chart
– 40° C to + 85° C
Outputs 1 – 4: 0.02% /°C

GENERAL SPECIFICATIONS

Means of Protection
Primary to Secondary
Primary to Ground
Secondary to Ground
Dielectric Strength(15)
Reinforced Insulation
Basic Insulation
Operational Insulation
Leakage Current
Earth Leakage
Touch Current

Power Fail Signal

Remote On/Off (optional)
Remote Sense
Mean-Time Between Failures
Weight

2MOPP (Means of Patient Protection)
1MOPP (Means of Patient Protection)
Operational Insulation(Consult factory for 1MOOP or 1MOPP)
(See Datasheet)
5656 VDC, Primary to Secondary, 1 Sec.
2545 VDC, Primary to Ground, 1 Sec.
707 VDC, Secondary to Ground, 1 Sec.

less than 300uA NC, less than 1000uA SFC
less than 100uA NC, less than 500uA SFC

Logic low with input power failure 10 mS
minimum prior to Output 1 dropping 1%
Contact closure shuts off all outputs
250mV compensation of output cable losses
100,000 Hours min., MIL-HDBK-217F, 25° C, GB
1.15 Lbs. Open Frame/ 1.82 Lbs. Chassis and Cover

Manufacturer Part Number: REL-150-1006-CHCO
Manufacturer: Electronic Components

Product Enquiry