background image

BEG50

0

K

-

A

Tel

:+86-755-89888888 

E

-

mail

:

bydenergy

@

byd

.

com

Http

://

www

.

bydenergy

.

com

System

 

Diagram

 

 

Isolated  Grid-tied Converter

Wide-range of DC input voltage 

High Efficiency, High Power Factor 

Advanced

 

IGBT power devices

Perfect

 

DC/AC Protection

RS

485/

CAN

/

Ethenet/

GSM communication interface(optional)

Auxiliary

 

electric

 

heating

(

optional

)

Low voltage ride-through, 

reactive power 

 

adjustable, act

CQC Certification

Transformer Isolated

500

KW

AC

EMI

Filter

Isolated transfomer

AC Fuse

DC 

breaker

Contactor

DC

EMI

Filter

Sine

Filter

DSP Control

A

B

C

N

PE

Interface For 

Communication

Inverter

 Bridge

Contactor

AC Fuse

AC 

breaker

DSP control, true sine-wave outputs

BEG500K-A-html.html
background image

 

DC Side Data

AC Side Data

System

 

Data

Display

 

and

 

Communication

Protect

 

Function

Max

DC

 

Voltage

DC

 

Voltage

 

Range

Nominal

 

Power(Charge)

 

Nominal

 

Power(Discharge)

 

Max

Permissible

 

DC

 

Current

Nominal

 

AC

 

Power(Discharge)

Nominal

 

AC

 

Power

(

Charge

)

Permissible

 

Grid

 

Voltage

;

Range

Permissible

 

Grid

 

Frequency

Range

Power

 

Factor

Max

 

Efficiency

Display

Communication

 

Method

Short

 

Circuit

 

Protection

Overload

 

Protection

DC

 

Over

/

Under

 

Voltage

 

Protection

AC

 

Over

/

Under

 

Voltage

 

Protection

AC

 

Over

/

Under

 

Frequency

 

Protection

Over

 

Temperature

 

Protection

DC

 

Reverse

 

Connection

 

Protection

BSG

20

KTL

-

E

1000

Vdc

700~900

Vdc

500kW

520

kW

820A

500

kW

520kW

 400

V

;340-440

V

50

Hz

;48-50.5

Hz

≥0.99(

Nominal

 

power

)

97.5%

Isolation Method

Degree

 

of

 

Protection

 

Cooling

 

Method

Noise

 

Transformer

 

isolated

Ip

20 (

Indoor

 )

Controlled forced-air cooling

<70

dB

Touch

 

controlpanel

Ethernet

 

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Technical Data

888

THD

 

of

 

AC

 

Current

<5%(

Nominal

 

power

)

Islanding

 

Protection

Active

 

and

 

passive

 

control

Mechanical

 

Dimensions

Dimension

L

×

D

×

H

3920×1040×2200

mm

Weight

4700

kg

Reference

 

Standard

GB/T 19939-2005

IEC

 62109 ;

IEC 62116

Permissible Altitude

Permissible 

Ambient

 

Temperature

Permissible Relative Humidity

0~

95%,(Non-condensing)

-25~+55℃

2000M