background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

COPPER SUBSTATION

Introduction

Type 

NAS

  Cable to Pad

Type 

NA

  Tube to Flat

Type 

NAH

  Cable to Pad

Type 

N2AH

  Cable to Flat

Type 

VA

  Cable to Flat 

Type 

VVA

  Cable to Flat

Type 

XA

  Tube to Flat, Expandable

Type 

NT

  Tube to Tube

Type 

NSNT

  Tube or Cable to Cable

Type 

NHNT

  Tube to Cable

Type 

VT

  Cable to Cable

Type 

NS

  Tube to Tube

Type 

XP

  Tube to Tube

Type 

UH

  Tube

Type 

UHR

  Tube or Cable

Type 

LH, LHR

  Tube or Cable

Type 

FD

  Stud to Flat Bar

Type 

NDR

  Cable, Tube, Flat Bar

Type 

QGFL

  Cable to Flat

Type 

FCB

 

Transformer Tap Adapter

Type 

E-C-G

  Transformer Tap Adapter

Type 

HFBW

  Bar Clamp

Type 

HFB-P1

 

  Bar Clamp Components

Type 

HFB-N

  Tap Pad Adapter

Type 

NNT

  Tube to Tube

Type 

NNTR

  Cable to Cable

Type 

NNTR

  Tube to Cable

TABLE OF CONTENTS

L-3

L-4

L-5

L-6

L-7

L-8

L-9

L-10

L-11

L-12

L-13

L-14

L-15

L-16

L-17

L-17

L-18

L-19

L-20

L-21

L-22

L-22

L-23

L-24

L-24

L-25

L-26

L-27

Substation

 Bolted

L-1

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

Type 

NS-A

  Tube to Tube

Type 

NA-A

  Tube to Flat

Type 

XA-A

  Tube to Flat

Type 

NAR

  Cable to Flat

Type 

NBC-A

  Tube to Flat

Type 

UHG

  Fixed or Rigid Pipe to Base

Type 

UHKR-A

  Tube or Cable

Type 

LB-A

  Pipe End Cap

Type 

WAS-A

  Tube to Pad

Type 

WASC-A-N

  Tube to Pad

Type 

WG

  Stud to Tube

L-28

L-28

L-29

L-30

L-31

L-32

L-33

L-34

L-35

L-36

L-37

Substation 

Bolted

L-2

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

Substation

Bolted

COPPER

SUBSTATION

CONNECTORS

INTRODUCTION

BURNDY

®

  electrical  connectors 

are  designed  to  be  installed  with  a 

minimum of effort, to run cooler than 

the  conductors  being  joined  and  to 

provide optimum performance under 

all operating conditions.

To achieve this type of performance, 

extensive research and development 

time  is  spent  by  BURNDY

®

 

engineers  and  scientists  to  improve 

manufacturing techniques, materials 

and designs. As these improvements 

become 

available, 

they 

are 

incorporated  into  both  existing  and 

new  product  lines.  This  continuous 

program  of  product  innovation 

and  improvement  insures  that,  as 

new  and  more  critical  applications 

evolve, high quality connectors from 

BURNDY

®

  will  be  available  to  meet 

the need.

N-Line  connectors  are  two-piece 

copper  alloy  castings  assembled 

with  DURIUM™  (silicon  bronze) 

hex bolts, nuts and washers. They 

are available for connecting tube or 

cable.

The Variline incorporates a modified 

V-bolt as the clamping element for 

heavy-duty  applications.  This  line 

is  particularly  suited  for  use  with 

flexible and extra flexible cables.

Flat  pad  connectors  used  to 

join  cable  or  tubing  terminals  to 

equipment studs.

A  variety  of  bus  supports  are  also 

available  for  tube  or  cable.  Some 

can be adjusted for either a rigid or 

slide-fit by rotating the clamping cap 

180°.

Expansion  connectors  are  used 

to  absorb  the  stress  imposed  on 

the bus by settling ground, thermal 

expansion and shocks, as in circuit 

breaker  operations.  The  flexible 

elements  are  flat-tinned,  copper 

braid, with sufficient cross sectional 

area to carry the rated current of the 

conductors being joined.

L-3

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE NAS

BOLTED TERMINALS

For Use On Cable To Pad

High  copper  alloy  reversible  cap  terminal  for 

joining a wide range of cable to pads. Tongue is 

side  formed  to  provide  adequate  clearance  and 

terminal is designed for one- wrench installation.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

• 

Plated versions: add the required suffix 

to the catalog number. -TN for regular tin 

plating.

• 

Please contact factory for other sizes, 

combinations and availability.

• 

See NAH family for heavy duty versions.

Substation 

Copper Bolted Terminals | 230 kV

Catalog 

Number

Fig. #

Copper Stranded 

Range

Copper Solid 

Range

B

Dia.

L

C

T

W

NAS29-2N

1

6 AWG-250 kcmil

6 AWG-4/0 AWG

2.38

3/8

5.62

1.50

0.25

2.00

NAS29-34N

2

2.38

3/8

5.62

3.00

0.25

2.00

NAS29-N

2.38

3/8

3.88

1.25

0.25

2.00

NAS34-2N

1

1/0 AWG-500 kcmil

1/0 AWG-4/0 AWG

2.38

3/8

5.62

2.00

0.31

2.20

NAS34-34N

2

2.38

3/8

5.62

3.00

0.25

2.20

NAS34-N

2.38

3/8

4.12

1.50

0.25

2.20

NAS40-2N

1

2/0 AWG-800 kcmil

2/0 AWG-4/0 AWG

2.62

3/8

5.88

2.00

0.38

2.44

NAS40-34N

2

2.62

3/8

5.88

3.00

0.31

2.44

NAS40-44N

3

2.62

3/8

6.88

4.00

0.31

2.44

L-4

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE NA

TERMINAL

For Copper Tube to Flat

High copper alloy terminal for joining copper tube 

to a flat pad. Letter “N” on end of catalog number 

indicates  pad  drilled  to  NEMA  standards.  One-

wrench installation.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  Plated versions: add the required   

    suffix to the catalog number. -TN for 

    regular tin plating.

•  Please contact factory for other 

    sizes, combinations and availability.

Substation 

Copper Bolted Terminals | 230 kV

Catalog 

Number

Fig. #

Copper Pipe 

(Std or EH)

B

J

 Dia.

L

H

C

T

W

NA122N

1

3/8 IPS

1.38

3/8

3.75

1.50

1.50

0.25

2.13

NA132N

1

1/2 IPS

2.00

5.25

1.75

1.50

0.38

2.25

NA142N

1

3/4 IPS

5.25

2.00

1.63

0.38

2.44

NA144N

2

4.50

2.00

3.13

0.38

2.44

NA152N

1

1 IPS 

5.25

2.06

1.88

0.38

2.75

NA154N

2

5.25

2.06

3.00

0.38

2.75

NA162N

1

1 1/4 IPS

2.69

1/2

5.94

2.56

2.25

0.44

3.50

NA164N

2

5.94

2.56

3.00

0.44

3.50

NA172N

1

5.94

2.75

2.50

0.50

3.94

NA1744NHQ

3

1 1/2 IPS

7.07

3.09

4.00

0.50

3.82

NA174N

2

1 1/4 IPS

5.94

2.75

3.00

0.50

3.94

NA182N

1

2 IPS

5.94

3.12

2.75

0.50

4.62

NA184N

2

5.94

3.13

3.13

0.50

4.63

NA1944N

3

2 1/2 IPS 

7.19

3.74

4.00

0.69

5.24

NA1944NHQ

3

7.09

3.96

4.00

0.75

5.12

NA194N

2

5.94

3.69

3.75

0.69

5.25

NA194N90CG2

2

2 1/2 IPS

6.50

3.62

3.75

0.69

5.25

NA204N

2

3 IPS 

3.25

5/8

6.56

4.38

4.38

0.69

6.19

NA214N

2

3 1/2 IPS

6.56

4.94

4.75

0.81

6.81

NA224N

2

4 IPS 

6.56

5.50

5.25

0.81

7.44

L-5

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE NAH

BOLTED TERMINALS

For Use On Cable To Pad

High copper alloy terminal for joining a wide range 

of cable to equipment pads. Tongue is side formed 

to  provide  adequate  clearance  and  terminal  is 

designed for one-wrench installation.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

• 

Plated versions: add the required suffix 

to the catalog number. -TN for regular tin 

plating.

• 

Please contact factory for other sizes, 

combinations and availability

Substation 

Copper Bolted Terminals | 230 kV

Catalog 

Number

Fig. #

Copper 

Stranded 

Range

Copper 

Solid 

Range

B

J

Dia.

L

C

T

W

NAH29-2N

1

6 AWG-250 kcmil

6 AWG-4/0 AWG

2.62

1/2

5.88

1.50

0.25

2.44

NAH29-34N

2

3.00

NAH34-2N

1

1/0 -500 kcmil

1/0 AWG-4/0 AWG

2.00

0.31

2.56

NAH34-34N

2

3.00

0.25

NAH40-2N

1

2/0 AWG-800 kcmil

3/0 AWG-4/0 AWG

2.00

0.38

2.81

NAH40-34N

2

3.00

0.31

NAH404-4N

3

6.88

4.00

NAH44-2N

1

4/0 AWG-1000 kcmil

N/A

2.88

6.12

2.00

0.44

2.88

NAH44-34N

2

3.00

0.38

NAH44-44N

3

7.12

4.00

0.31

NAH46-2N

1

1000 kcmil-1500 kcmil

3.06

6.31

2.00

0.50

3.19

NAH46-34N

2

3.00

0.41

NAH46-44N

3

7.31

4.00

0.38

NAH48-2N

1

500 kcmil-2000 kcmil

3.25

6.50

2.00

0.69

3.38

NAH48-34N

2

3.00

0.50

NAH48-44N

3

7.50

4.00

0.44

NAH48-62N

1

2000 kcmil-2500 kcmil

3.75

5/8

7.12

3.00

0.63

3.96

NAH486-34N

2

L-6

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE N2AH

BOLTED TERMINALS

For Two Copper Cables to Flat

High  copper  alloy  reversible  cap  terminal  for 

joining a wide range of cable to  pads. Tongue is 

side  formed  to  provide  adequate  clearance  and 

terminal is designed for one wrench installation.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

• 

Plated versions: add the required suffix 

to the catalog number. -TN for regular tin 

plating.

• 

Please contact factory for other sizes, 

combinations and availability.

Substation 

Copper Bolted Terminals | 230 kV

Catalog 

Number

Fig. #

Copper 

Stranded 

Range

Copper 

Solid 

Range

B

Dia.

L

C

T

W

U

N2AH29-2N

1

6 AWG-250 kcmil

6 AWG-4/0 AWG

2.62

1/2

5.87

1.50

0.32

4.88

2.44

N2AH29-34N

2

6 AWG-250 kcmil

6 AWG-4/0 AWG

2.62

1/2

5.87

3.00

0.32

4.88

2.44

N2AH34-2N

1

1/0 AWG-500 kcmil

1/0 AWG-4/0 AWG

2.62

1/2

5.87

2.00

0.32

5.44

2.88

N2AH34-34N

2

1/0 AWG-500 kcmil

1/0 AWG-4/0 AWG

2.63

1/2

6.13

3.00

0.38

5.40

2.88

N2AH34-44N

3

1/0 AWG-500 kcmil

1/0 AWG-4/0 AWG

2.63

1/2

7.00

4.00

0.38

5.38

2.88

N2AH40-34N

2

2/0 AWG-800 kcmil

2/0 AWG-4/0 AWG

2.63

1/2

5.88

3.00

0.38

5.70

2.92

N2AH44-34N

2

4/0 AWG-1000 kcmil

4/0 AWG

2.88

1/2

6.38

3.00

0.50

6.12

3.12

N2AH44-44N

3

4/0 AWG-1000 kcmil

4/0 AWG

2.88

1/2

7.32

4.00

0.50

6.12

3.12

N2AH44-44NHQ

3

4/0 AWG-1000 kcmil

4/0 AWG

2.88

1/2

7.20

4.00

0.50

6.12

3.12

N2AH46-44N

3

1000 kcmil-1500 kcmil

N/A

3.07

1/2

7.46

4.00

0.75

6.50

3.36

N2AH48-44N

3

1000 kcmil-1500 kcmil

N/A

3.25

1/2

7.62

4.00

0.75

9.50

4.00

L-7

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE VA

VARILUG™

For Use On Copper Cable

High copper alloy terminal for joining a wide range 

of  cable  to  equipment  pads  or  bar.  Particularly 

suitable  for  use  on  extra  flexible  cable.  One-

wrench  installation.  Type  VVA,  twin  elements 

secure  joint  against  vibration  and  flexing. 

Particularly recommended for use on extra flexible 

cables. One-wrench installation.

Material:  Bronze Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes :

 

• 

Plated versions: add the required suffix 

to the catalog number. -TN for regular tin 

plating.

• 

Please contact factory for other sizes, 

• 

combinations and availability

• 

Choose type VVA with twin elements for 

additional joint strength against vibration 

and flexing. Particularly recommended for 

use on flexible cables.

Substation

VARILUG™ | 230 kV

Catalog 

Number *

Fig. #

Copper 

Stranded 

Range

Copper 

Solid 

Range

C

B

J

Dia.

L

T

W

VA4C

8 AWG-4 AWG

8 AWG-4 AWG

0.75

0.69

7/16

2.38

0.22

0.81

VA2C

8 AWG-2 AWG

8 AWG-2 AWG

0.81

0.81

3/8

2.72

0.25

1.00

VA25

6 AWG-1/0 

6 AWG-1/0 AWG

0.88

0.88

3/8

2.88

0.25

1.19

VA252

0.88

0.88

3/8

3.63

0.25

1.19

VA28

1/0 AWG-4/0 AWG

1/0 AWG-4/0 AWG

1.06

1.09

3/8

2.84

0.31

1.69

VA28-2N

1

1.06

1.09

3/8

4.94

0.31

1.69

VA30

1/0 AWG-300 kcmil

1/0 AWG-4/0 AWG

1.13

1.09

3/8

3.22

0.31

1.91

VA30-2N

1

1.12

1.09

7/16

5.19

0.31

1.91

VA34

300 kcmil-500 kcmil

N/A

1.38

1.31

1/2

3.81

0.38

2.22

VA34-2N

1

1.38

1.31

1/2

5.38

0.38

2.22

VA344

1.88

1.31

7/16

4.22

0.38

2.22

VA40

500 kcmil-800 kcmil

1.63

1.34

9/16

4.47

0.38

2.63

VA40-2N

1

1.62

1.34

9/16

5.81

0.38

2.62

VA404

1.88

1.34

9/16

4.72

0.38

2.63

VA40-4N

2

3.00

1.34

9/16

5.81

0.38

2.62

VA44

750 kcmil-1000 kcmil

1.88

1.41

5/8

4.78

0.50

2.88

VA444

2.13

1.41

5/8

5.16

0.50

2.88

VA462N

1

1000 kcmil-1500 kcmil

2.25

2.00

5/8

6.44

0.56

3.25

*    “N” indicates NEMA standard stud holes.

L-8

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE VVA

VARILUG™

For Use On Copper Cable

High copper alloy terminal for joining a wide range 

of  cable  to  equipment  pads  or  bar.  Particularly 

suitable  for  use  on  extra  flexible  cable.  One-

wrench installation.

Material:  Bronze Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  Plated versions: add the required suffix 

    to the catalog number. -TN for regular 

    tin plating

•  Please contact factory for other sizes, 

    combinations and availability

Substation

 VARILUG™ | 230 kV

Catalog 

Number *

Fig. #

Copper 

Stranded Range

Copper 

Solid Range

C

B

Dia.

L

T

W

VVA2C

8 AWG-2 AWG

8 AWG-2 AWG

0.81

0.81

3/8

4.06

0.25

1.00

VVA25

6 AWG-1/0 

6 AWG-1/0 AWG

0.88

0.88

3/8

4.31

0.25

1.19

VVA25-2

1/0 AWG-4/0 AWG

0.88

0.88

3/8

5.06

0.25

1.19

VVA28

1/0 AWG-4/0 AWG

1.06

1.09

3/8

4.13

0.31

1.69

VVA28-2N

1

1.06

1.09

3/8

6.19

0.31

1.69

VVA30

300 kcmil

1/0 AWG-4/0 AWG

1.13

1.09

7/16

4.63

0.31

1.94

VVA30-2N

1

1.13

1.09

7/16

6.56

0.31

1.94

VVA30-4N

2

3.00

1.09

7/16

6.75

0.38

1.91

VVA34

300 kcmil-500 kcmil

N/A

1.38

1.31

1/2

5.31

0.38

2.25

VVA34-2N

1

1.30

1.31

1/2

6.88

0.38

2.22

VVA34-4

1.88

1.31

7/16

5.75

0.38

2.25

VVA34-4N

2

3.13

1.31

7/16

7.00

0.38

2.38

VVA40

500 kcmil-800 kcmil

1.63

1.34

9/16

6.38

0.38

2.63

VVA40-2N

1

1.62

1.34

9/16

7.69

0.38

2.62

VVA40-4N

2

3.00

1.34

9/16

7.69

0.38

2.62

VVA40-4NCG1

3.50

0.88

9/16

7.69

0.38

2.62

VVA44-2N

1

750 kcmil-1000 kcmil

1.88

1.41

5/8

8.12

0.50

2.88

VVA44-4N

2

3.00

1.41

5/8

8.06

0.50

2.88

VVA46-2N

1

1000 kcmil-1500 kcmil

2.25

2.00

5/8

8.69

0.56

3.25

VVA46-4NCG2

3.50

2.00

5/8

8.75

0.56

3.25

VVA46-4NCG4

3.50

2.00

5/8

5.50

0.56

3.23

VVA48-2N

1

1500 kcmil-2000 kcmil

2.62

2.25

3/4

9.23

0.62

3.75

*    “N” indicates NEMA standard stud holes.

L-9

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE XA

BOLTED EXPANSION TERMINALS

For Copper Tube to Flat

High copper alloy expansion terminal for tube to flat. 

Provides for longitudinal movement of tubing. Extra 

flexible braid carries full load of joint. One-wrench 

installation. 

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  Plated versions: add the required  

    suffix to the catalog number. -TN for 

    regular tin plating.

•  Please contact factory for other 

    sizes, combinations and availability.

•  Installation instructions available 

    upon request.

Substation 

Copper  Expansion Terminals | 230 kV

Catalog 

Number

Fig. #

Copper Pipe 

(Std)

Copper Pipe 

(EH)

B

C

J

Dia.

L

H

W

XA132N

1

1/2 IPS

N/A

3.00

1.50

3/8

12.00

3.88

3.06

XA142N

1

3/4 IPS

1.63

3/8

12.00

4.06

3.13

XA144N

2

3.00

3/8

12.50

4.12

3.12

XA152N

1

1 IPS

1.88

3/8

12.75

4.31

3.13

XA154N

2

3.00

3/8

12.75

4.31

3.13

XA162N

1

1 1/4 IPS

3.50

2.25

1/2

14.50

5.81

4.31

XA164N

2

3.00

1/2

14.75

5.81

4.31

XA172N

1

1 1/2 IPS

2.50

1/2

15.00

6.06

4.31

XA174N

2

3.00

1/2

15.25

6.06

4.31

XA184N

2

2 IPS

3.00

1/2

15.25

7.00

4.62

XA194N

2

2 1/2 IPS

4.00

3.75

1/2

16.13

7.50

5.25

XA204N

2

3 IPS

4.38

5/8

16.69

7.94

6.50

XA214N

2

3 1/2 IPS

4.75

5/8

16.94

8.25

6.81

XA224N

2

4 IPS

5.25

5/8

17.00

9.44

7.44

XA574N

2

N/A

1 1/2 IPS

3.50

3.00

1/2

14.38

6.44

4.31

XA594N

2

2 1/2 IPS

4.00

3.75

1/2

14.75

9.56

5.25

L-10

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE NT

T-CONNECTORS

For Use On Tube To Tube T 

(6 BOLTS)

High copper alloy T-Connector for tubing run and 

tap. Slots between bolts provide independent high-

pressure areas of contact. One-wrench instiallation.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  Plated versions: add the required suffix 

    to the catalog number. -TN for regular 

    tin plating.

•  Items with -HC suffix have hex head 

    bolts; items without the suffix can be 

    either hex head or oval shank head. 

    Both head styles are one wrench 

    installation and offer the same clamping 

    force and functionalities.

•  Please contact factory for other sizes, 

    combinations and availability.

•  One-wrench installation.

Substation

Copper Bolted T-Connectors | 230kV

Catalog 

Number

A

Run Copper 

Pipe 

AA

Tap Copper

 Pipe 

J

Dia.

BB

L

H

W

NT1313

1/2 IPS 

1/2 IPS 

2.00

3/8

2.00

4.13

1.94

2.44

NT1413

3/4 IPS

1/2 IPS

2.00

4.13

1.94

2.25

NT1414

3/4 IPS

2.00

4.13

1.94

2.44

NT1514

1 IPS

3/4 IPS

2.00

4.38

2.13

2.44

NT1515

1 IPS

2.00

4.44

2.13

2.75

NT1614

1 1/4 IPS

3/4 IPS

2.00

4.75

2.44

2.44

NT1615

1 IPS

2.00

4.75

2.44

2.75

NT1616

1 1/4 IPS

2.69

1/2

2.69

5.69

2.63

3.50

NT1714

1 1/2 IPS

3/4 IPS

2.00

3/8

2.00

5.06

2.69

2.44

NT1715

1 IPS

2.00

5.06

2.69

2.75

NT1717

1 1/2 IPS

2.69

1/2

2.69

6.06

2.75

3.94

NT1816

2 IPS

1 1/4 IPS

2.69

6.56

2.69

3.50

NT1817

1 1/2 IPS

2.69

6.63

3.25

3.94

NT1818

2 IPS

3.06

2.69

6.69

3.31

4.62

NT1919

2 1/2 IPS

2 1/2 IPS

3.63

2.69

7.25

3.88

5.25

NT2020

3 IPS

3 IPS

4.31

5/8

3.25

8.63

4.63

6.19

NT2121

3 1/2 IPS

3 1/2 IPS

4.88

3.25

9.25

5.19

6.81

NT2222

4 IPS

4 IPS

5.44

3.25

9.81

5.75

7.44

L-11

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE NSNT

T-CONNECTORS

For Use On Tube Or Cable To 

Cable T

High  copper  alloy  reversible  T-Connector  for 

joining  a  wide  range  of  run  and  tap  cables. 

Connector is designed for one-wrench installation. 

“S” standard 3/8 in hardware and “H” heavy duty 

1/2 in hardware.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

• 

Plated versions: add the required suffix 

to the catalog number. -TN for regular tin 

plating.

• 

Please contact factory for other sizes,    

combinations and availability.

• 

One-wrench installation.

Substation

Copper Bolted T-Connectors | 230kV

1 Complete cable range may be accommodated by 

reversing cap.

Catalog 

Number

A

Pipe Run

A

Cable  Run

AA

Cable Tap Range

J

Dia.

BB

L

W

NSNT1329

1/2 IPS

N/A

6 AWG-250 kcmil

2.00

3/8

2.38

5.08

2.00

1.96

NSNT1429

3/4 IPS

6 AWG-250 kcmil

2.00

3/8

2.38

5.08

2.00

1.96

NSNT1434

1/0 AWG-500 kcmil

2.00

3/8

2.38

5.08

2.10

2.20

NSNT1529

1 IPS

6 AWG-250 kcmil

2.00

3/8

2.38

5.34

2.00

1.96

NSNT1629

1 1/4 IPS

6 AWG-250 kcmil

2.00

3/8

2.38

5.78

2.37

1.96

NSNT2929

6 AWG-250 kcmil

6 AWG-250 kcmil

2.38

3/8

2.38

4.60

1.75

1.96

NSNT3429

1/0 AWG-500 kcmil

6 AWG-250 kcmil

2.38

3/8

2.38

4.84

2.00

1.96

NSNT3434

1/0 AWG-500 kcmil

2.38

3/8

2.38

4.84

2.00

2.20

1

L-12

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE NHNT

T-CONNECTORS

For Use On TUBE TO CABLE T

High  copper  alloy  reversible  T-Connector  for 

joining a wide range of run pipe and tap cables. 

Connector is designed for one-wrench installation.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  Plated versions: add the required suffix 

    to the catalog number. -TN for regular tin 

    plating.

•  Please contact factory for other sizes, 

    combinations and availability.

•  One-wrench installation.

Catalog 

Number

Pipe Run

AA

Cable Tap Range

B

J

Dia.

BB

H

W

NHNT1429

3/4 IPS

6 AWG-250 kcmil

2.25

1/2

2.62

5.82

2.32

2.44

NHNT1434

1/0 AWG-500 kcmil

2.25

1/2

2.62

5.82

2.42

2.56

NHNT1529

1 IPS

6 AWG-250 kcmil

2.25

1/2

2.62

5.92

2.57

2.44

NHNT1534

1/0 AWG-500 kcmil

2.25

1/2

2.62

5.92

2.57

2.56

NHNT1540

2/0 AWG-800 kcmil

2.25

1/2

2.62

5.92

2.60

2.78

NHNT1629

1 1/4 IPS

6 AWG-250 kcmil

2.69

1/2

2.62

6.32

2.57

2.44

NHNT1634

1/0 AWG-500 kcmil

2.69

1/2

2.62

6.32

2.60

2.56

NHNT1640

2/0 AWG-800 kcmil

2.69

1/2

2.62

6.32

2.68

2.78

NHNT1644

4/0 AWG-1000 kcmil

2.69

1/2

2.88

6.58

2.69

2.90

NHNT1729

1 1/2 IPS

6 AWG-250 kcmil

2.69

1/2

2.62

6.76

2.70

2.44

NHNT1734

1 1/2 IPS 

1/0 AWG-500 kcmil

2.69

1/2

2.62

6.76

2.70

2.56

NHNT1740

1 1/2 IPS

2/0 AWG-800 kcmil

2.69

1/2

2.62

6.76

2.78

2.78

NHNT1744

4/0 AWG-1000 kcmil

2.69

1/2

2.88

7.02

2.80

2.90

NHNT1829

2 IPS

6 AWG-250 kcmil

2.69

1/2

2.62

7.44

3.06

2.44

NHNT1834

1/0 AWG-500 kcmil

2.69

1/2

2.62

7.44

3.06

2.56

NHNT1840

2/0 AWG-800 kcmil

2.69

1/2

2.62

7.44

3.06

2.78

NHNT1844

4/0 AWG-1000 kcmil

2.69

1/2

2.88

7.70

3.06

2.90

NHNT1846

1000 kcmil-1500 kcmil

2.69

1/2

3.06

7.88

3.23

3.16

NHNT1929

2 1/2 IPS

6 AWG-250 kcmil

2.69

1/2

2.62

8.06

3.64

2.44

NHNT1934

1/0 AWG-500 kcmil

2.69

1/2

2.62

8.06

3.64

2.56

NHNT1940

2/0 AWG-800 kcmil

2.69

1/2

2.62

8.06

3.64

2.78

NHNT1944

4/0 AWG-1000 kcmil

2.69

1/2

2.88

8.32

3.64

2.90

NHNT1946

1000 kcmil-1500 kcmil

2.69

1/2

3.06

8.50

3.64

3.16

NHNT2040

3 IPS

2/0 AWG-800 kcmil

2.69

1/2

2.88

8.69

4.26

2.78

NHNT2044

4/0 AWG-1000 kcmil

2.69

1/2

5.75

8.95

4.26

2.90

NHNT2229

4 IPS

6 AWG-250 kcmil

3.25

1/2

2.63

10.38

4.26

2.50

1

1 Complete cable range may be accommodated by 

reversing cap.

Substation

Copper Bolted T-Connectors | 230kV

L-13

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE VT

T-CONNECTORS

For Use On Copper Cable to Cable

High copper alloy T-connector for cable run, cable 

tap. V-bolt clamping elements accommodate large 

range of cable and are particularly suited for extra 

flexible cable. One-wrench installation.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  Plated versions: add the required  suffix 

    to the catalog number. -TN for regular 

    tin plating.

•  Please contact factory for other sizes,  

    combinations and availability.

•  One-wrench installation.

Substation

Copper Bolted T-Connector | 230kV

Catalog 

Number

A - Cable 

Run Range

AA - Cable 

Tap Range

Dia.

JJ 

Dia.

L

H

W

VT2C2C

8 AWG-2 AWG

8 AWG-2 AWG

5/8

5/8

2.31

1.38

1.00

VT2525

6 AWG-1/0 AWG

6 AWG-1/0 AWG

3/4

3/4

1.37

0.38

0.56

VT2825

1/0 -4/0 AWG

6 AWG-1/0 AWG

3/8

3/4

3.12

1.62

1.25

VT2828

1/0 -4/0 AWG

1/0 -4/0 AWG

3/8

3/8

2.94

0.38

0.31

VT3028

1/0 -300 kcmil

1/0 -4/0 AWG

7/16

3/8

3.19

1.88

1.69

VT4034

500 kcmil-800 kcmil

300 kcmil-500 kcmil

9/16

1/2

4.13

2.56

2.25

VT4430

750 kcmil-1000 kcmil

1/0 -300 kcmil

5/8

7/16

4.25

2.88

1.94

VT4434

300 kcmil-500 kcmil

5/8

1/2

4.38

3.34

2.25

VT4440

500 kcmil-800 kcmil

5/8

9/16

4.75

2.88

2.63

VT4444

750 kcmil-1000 kcmil

5/8

5/8

4.88

2.88

2.88

VT4628

1000 kcmil-1500 kcmil

1/0 -4/0 AWG

5/8

3/8

4.50

3.81

1.69

VT4630

1/0 -300 kcmil

5/8

7/16

4.63

3.81

1.94

VT4640

500 kcmil-800 kcmil

5/8

9/16

5.13

3.81

2.63

VT4830

1500 kcmil-2000 kcmil

1/0 -300 kcmil

3/4

7/16

5.13

4.25

1.94

VT4840

500 kcmil-800 kcmil

3/4

9/16

5.63

4.25

2.63

VT4844

750 kcmil-1000 kcmil

3/4

5/8

5.75

4.25

2.88

VT4848

1500 kcmil-2000 kcmil

3/4

3/4

6.25

4.25

3.75

L-14

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE NS

COUPLERS

For Use On Straight Tube To Tube

High copper alloy coupler for joining equal sizes 

of tube end to end. Slots between bolts provide 

independent high pressure areas of contact. One-

wrench installation.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  Plated versions: add the required suffix 

    to the catalog number. -TN for regular 

    tin plating.

•  W for extra thick tin plating (including    

    hardware).

•  Items with -HC suffix have hex head 

    bolts; items without the suffix can be  

    either hex head or oval shank head. 

    Both head styles are one wrench 

    installation and offer the same clamping 

    force and functionalities.

•  Please contact factory for sizes, 

    combinations and availability.

Substation

Copper Bolted Couplers | 230kV

Catalog Number

Copper Conductor

B

J  Dia.

L

H

W

NS1212

3/8 IPS

1.50

3/8

3.00

1.44

1.94

NS1313

1/2 IPS

1.63

3/8

3.25

1.69

2.25

NS14148HC

3/4 IPS

2.69

1/2

5.75

2.32

2.81

NS1414HC

2.69

3/8

5.38

2.32

2.81

NS1515

1 IPS

2.13

3/8

4.25

2.13

2.75

NS1515HC

2.69

1/2

5.62

2.32

3.25

NS1515HCHQ

2.69

1/2

5.63

2.36

3.22

NS1616HC

1 1/4 IPS

2.69

1/2

5.75

2.57

3.50

NS1717

1 1/2 IPS

2.88

1/2

5.75

2.75

3.94

NS1717HC

2.69

1/2

5.75

2.81

3.94

NS1717HCHQ

2.69

1/2

5.75

2.61

3.94

NS1818

2 IPS

2.88

1/2

5.75

3.31

4.63

NS1818CG2

2.69

1/2

5.36

3.06

4.62

NS1818HC

2.69

1/2

5.75

3.31

4.62

NS1919

2 1/2 IPS

2.88

1/2

5.75

3.88

5.25

NS1919HC

2.69

1/2

5.75

3.96

5.25

NS1919HCHQ

2.69

1/2

5.75

3.56

5.18

NS2020

3 IPS

3.63

5/8

7.25

4.63

6.19

NS2020HC

3.25

5/8

7.25

4.64

6.19

NS2121

3 1/2 IPS

4.00

5/8

8.00

5.19

6.81

NS2121HC

3.25

5/8

7.25

5.20

6.81

NS2222

4 IPS 

4.25

5/8

8.50

5.75

7.44

NS2222HC

3.25

5/8

7.25

5.76

7.44

L-15

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE XP

EXPANSION COUPLERS

For Use On Copper Tube to Tube

High alloy copper expansion coupler for joining equal 

size  tube  on  end.  Extra  flexible  tinned  copper  braid 

allows longitudinal movement of the tube. Type XP has 

alignment guide. One-wrench installation. 

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  Items with “-HC” suffix have hex head 

    bolts; items without the suffix can be 

    either hex head or oval shank head. 

    Both head styles are one wrench 

    installation and offer the same clamping 

    force and functionalities.

•  Installation instructions available upon   

    request.

•  For other sizes or configurations, please 

    call factory.

Substation

Copper Bolted Expansion Coupler | 230kV

Catalog 

Number

Copper 

Pipe 

Size

Copper 

EH Pipe 

Size

B

Dia.

L

H

W

XP1313

1/2 IPS

3.00

3/8

8.75

3.88

3.06

XP1414

3/4 IPS

8.75

4.06

3.13

XP1515

1 IPS

9.50

4.31

3.13

XP1616

1 1/4 IPS

3.50

1/2

11.50

5.81

4.31

XP1717

1 1/2 IPS

12.00

6.44

4.31

XP1818

2 IPS

12.00

7.00

4.63

XP1919

2 1/2 IPS

4.00

13.00

8.50

5.25

XP1919HC

13.00

8.50

5.25

XP2020

3 IPS

5/8

13.50

7.75

6.50

XP2121

3 1/2 IPS

13.63

8.00

6.81

XP2222

4 IPS

13.63

9.06

7.44

XP5656

1 1/4 IPS

1 1/4 IPS

3.50

1/2

11.56

5.82

4.24

L-16

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE UH

BUS SUPPORTS

For Use On Copper Tube

High copper alloy bus support for mounting tube 

on a post or pedestal type insulator.  Single bolt 

allows rotation to any angle.  Rotate cap 180° for 

slip or rigid fit. One wrench installation. Supplied 

with  hardware  for  mounting  to  cap  of  insulator. 

Specify base mounting hardware, if required, by 

adding suffix “B” to catalog number.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  One wrench installation

•  Specify base mounting hardware, if 

    required, by adding suffix “-B” to catalog  

    number.

•  For other sizes and availability, please 

    contact factory.

Substation

Copper Bolted Bus Support | 230kV

Catalog 

Number

Copper Pipe 

Size

BC

J

Dia.

B

H

W

UH143

3/4 IPS 

3

2.00

3/8

2.50

2.88

2.63

UH153

1 IPS 

3

2.00

2.50

3.00

2.88

UH155

5

2.25

2.50

3.25

2.88

UH163

1 1/4 IPS

3

2.25

1/2

2.69

3.44

3.50

UH165

5

2.38

2.69

3.56

3.50

UH173

1 1/2 IPS

3

2.50

3.00

3.81

3.81

UH175

5

2.50

3.00

3.81

3.81

UH183

2 IPS

3

2.75

3.00

4.31

4.63

UH185

2 IPS 

5

2.75

3.00

4.31

4.63

UH193

2 1/2 IPS

3

3.13

3.00

5.00

5.25

UH195

5

3.13

3.00

5.00

5.25

UH203

3 IPS

3

3.63

5/8

3.25

5.81

6.19

UH205

5

3.63

3.25

5.81

6.19

UH225

4 IPS

5

4.50

3.25

7.25

7.50

TYPE UHR

BUS SUPPORTS

For Use On Copper Cable or Tube

High copper alloy bus support clamp for mounting 

a wide range of cable or tube on post or pedestal 

type insulators.  Single bolt allows rotation to any 

angle.  Supplied with hardware for mounting to cap 

of  insulator.  Specify  base  mounting  hardware,  if 

required, by adding suffix “-B” to catalog number.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  One wrench installation

•  Specify base mounting hardware, if 

    required, by adding suffix “-B” to catalog 

    number

•  For other sizes and availability, please   

    contact factory

*   With maximum conductor in place.

Catalog 

Number

Copper 

Stranded 

Range

Copper 

Pipe 

Size

BC

G

J

Dia.

B

H

W

UHR133

6 AWG -

500 kcmil

1/8 IPS - 

1/2 IPS

3

1.75

3/8

3.63

3.00

2.25

UHR135

5

2.13

3/8

3.63

3.38

2.25

UHR153

4/0 AWG - 

1250 kcmil

1/4 IPS -

1 IPS 

3

2.00

3/8

3.75

3.50

2.75

UHR153SS

3

2.00

3/8

3.75

3.50

2.75

UHR155

5

2.25

3/8

3.75

3.75

2.75

UHR173

750 kcmil -

2500 kcmil

3/4 IPS -

1 1/2 IPS

3

2.50

1/2

2.88

4.25

3.94

UHR175

5

2.50

1/2

2.88

4.25

3.94

UHR183

N/A

1 1/4 IPS - 

2 IPS

3

2.75

1/2

2.81

4.75

4.63

UHR185

5

2.75

1/2

2.81

4.75

4.63

L-17

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE LH

BUS SUPPORTS

For Use On Copper Cable or Tube

High  copper  alloy,  light  duty  bus  support  for 

mounting a wide range of cable or tube on post or 

pedestal type insulators. One-wrench installation. 

Supplied  with  hardware  for  mounting  to  cap  of 

insulator.  Specify  base  mounting  hardware,  if 

required, by adding suffix “-B” to Catalog No.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  One wrench installation.

•  Specify base mounting hardware, if 

    required, by adding suffix “-B” to catalog 

    number.

•  For applications requiring heavier duty 

    product, please see our UH product line.

•  For other sizes and availability, please 

    contact factory.

Substation

Copper Bolted Bus Support | 230kV

Catalog 

Number

Tube

Stranded 

Conductor

BC

J

Dia.

W

LH283

N/A

6 AWG-4/0 AWG

3

1.25

3/8 1.69 2.62 4.25

LH343

1/4 IPS -1/2 IPS  2/0 AWG-500 kcmil

3

1.38

3/8 1.38 2.50 4.25

LH453

1/2 IPS-1 IPS

500 kcmil-1250 kcmil

3

1.50

1/2 1.62 3.19 4.44

TYPE LHR

BUS SUPPORTS

For Use On Cable Or Tube To 

Insulator

High copper alloy, bus support for mounting a wide 

range of cable or tube on post or pedestal type 

insulators. One-wrench installation. Supplied with 

hardware for mounting to cap of insulator. 

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  One wrench installation.

•  Specify base mounting hardware, if 

    required, by adding suffix “-B” to Catalog

    Number.

•  For applications requiring heavier duty 

    product, please see our UH product line.

•  For other sizes and availability, please 

    contact factory.

Catalog 

Number

Tube

Stranded 

Conductor

BC 

J

Dia.

LHR293

1/8 IPS-1/4 IPS

8 AWG-250 kcmil

3

1.23 3/8 1.00

2.03

4.25

LHR443

1/4 IPS-3/4 IPS

4/0 AWG-1000 

kcmil

3

1.31

3/8 1.38

2.67

4.25

LHR445

5

1.33 3/8 1.00

2.51

6.25

L-18

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

Substation

Copper Bolted Stud Connector | 230kV

TYPE NDR

STUD CONNECTORS

For Copper Cable, Tube, Flat Bar

High copper alloy reversible and rotatable cap stud 

connector joins cable, tube and flat bar in-line or 

at right angles to equipment studs. Accommodates 

a  wide  range  of  cables  or  tubes.  One-wrench 

installation.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  Plated versions: add the required suffix 

    to the catalog number. -TN for regular 

    tin plating

•  Please contact factory for other sizes, 

    combinations and availability

•  One-wrench installation.

Catalog 

Number

Stud

 A

J

Dia.

Threads 

per inch

B

AA

Stranded Cable

JJ 

Dia.

L

H

NDR6334T13

1/2

3/8

13

1.62

6 AWG-500 kcmil

3/8

4.28

2.25

NDR6328T13

13

1.53

6 AWG-4/0 AWG

3/8

3.62

1.75

NDR6434T12

3/4

12

1.53

6 AWG-500 kcmil

3/8

4.09

2.24

NDR6434T16

16

1.53

3/8

4.09

NDR6428T16

16

1.53

6 AWG-4/0 AWG

3/8

3.60

1.74

NDR6444T16

16

1.53

2 AWG-1000 kcmil

1/2

4.66

2.82

NDR64534T14

7/8

14

1.53

6 AWG-500 kcmil

3/8

4.16

1.91

NDR6534T12

1

12

1.53

3/8

3.96

2.24

NDR6534T14

14

1.53

3/8

3.96

NDR6528T14

14

1.53

6 AWG-4/0 AWG

3/8

4.09

1.74

NDR6544T14

14

1.53

2 AWG-1000 kcmil

1/2

4.73

2.82

NDR65534T12

1-1/8

12

1.53

6 AWG-500 kcmil

3/8

3.97

2.24

NDR65528T12

12

1.53

6 AWG-4/0 AWG

3/8

4.12

1.75

NDR65544T12

12

1.53

2 AWG-1000 kcmil

1/2

4.66

2.82

NDR6748T12

1-1/2

1/2

12

2.03

4/0 AWG-2000 kcmil

1/2

5.78

3.25

NDR67548T12

1-3/4

12

2.03

1/2

6.56

2.51

NDR67544T12

12

2.03

2 AWG-1000 kcmil

1/2

6.28

3.12

NDR6848T12

2

12

2.03

4/0 AWG-2000 kcmil

1/2

6.56

2.82

NDR6844T12

12

2.03

2 AWG-1000 kcmil

1/2

6.12

2.88

NDR68544T12

2-1/4

12

2.50

1/2

6.81

3.12

L-19

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

Substation

Copper Bolted Stud Connector | 230kV

TYPE FD

STUD CONNECTORS

For Stud to Flat Bar

High  copper  alloy  stud  connector  allows  bolting 

cable  and  tubing  terminals  to  equipment  studs. 

Hex  head  captured  bolts  provide  one-wrench 

installation.  One  pad  contact  surface  is  on 

centerline of stud. Pad is finished on both sides. All 

pads are four hole NEMA drilled.

Material:  Copper Alloy

Hardware:  DURIUM™ Silicon Bronze

Notes : 

•  Plated versions: add the required suffix 

    to the catalog number. -TN for regular 

    tin plating

•  Pad is finished on both sides

•  Amperage rating given is for indoor 

    conditions

•  Please contact factory for other sizes, 

    combinations and availability

•  One-wrench installation

Catalog 

Number

Fig. 

#

Stud A

Threads per 

inch

Nominal 

Ampere 

Rating

B

J

Dia.

L

T

FD64C5T16

2

3/4

16

1000

1.75

3/8

5.72

5/16

FD65C6T14

2

1

14

1075

1.75

3/8

5.72

3/8

FD655C6

2

1-1/8

12

1075

1.75

3/8

5.80

3/8

FD655D6

3

12

1300

1.75

3/8

6.86

3/8

FD66C6

2

1-1/4

12

1075

1.75

3/8

5.78

3/8

FD66D6

3

12

1300

1.75

3/8

6.84

3/8

FD675C8

2

1-3/4

12

1100

2.18

1/2

6.32

1/2

FD675D8

3

12

1450

2.18

1/2

7.39

1/2

FD68C8

2

2

12

1100

2.18

1/2

6.35

1/2

FD68D8

3

12

1450

2.18

1/2

7.42

1/2

FD68D12

3

12

2100

2.18

1/2

7.42

3/4

FD685C8

2

2-1/4

12

1100

2.50

1/2

6.71

1/2

FD685D8

3

12

1450

2.50

1/2

7.77

1/2

FD685D12

3

12

2100

2.50

1/2

7.77

3/4

FD69C8

2

2-1/2

12

1100

2.50

1/2

6.77

1/2

FD69D8

3

12

1450

2.50

1/2

8.03

1/2

FD69D12

3

12

2100

2.50

1/2

8.03

3/4

FD70D12

3

3

12

2100

2.88

5/8

8.26

3/4

FD70D16

3

12

3000

2.88

5/8

8.24

1

L-20

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE QGFL

BARTAP™

For Copper Cable to Flat

High copper alloy BARTAP™ for joining a range of 

cable to bar or pad. One-wrench installation.

Material:  Copper Alloy

Notes : 

•  Can be installed side by side or in-line 

    on NEMA drilled bar.

Substation

Copper BARTAP™ | 230kV

Catalog 

Number

Copper 

Conductor

B

H

J

Dia. 

(Max)

W

QGFL1CB1

#10 Sol-#1 Str

1-1/8

1-7/8

3/8

1/4

1

QGFL1CB1T6

#10 Sol-#1 Str

1-1/8

2-3/8

3/8

3/4

1

QGFL26B1

#8 Sol-#2/0 Str

1-1/4

2-1/8

3/8

1/4

1-1/8

QGFL26B1T6

#8 Sol-#2/0 Str

1-1/4

2-5/8

3/8

3/4

1-1/8

QGFL26B2

#8 Sol-#2/0 Str

1-1/4

2-8/25

1/2

1/4

1-1/8

QGFL26B2T6

#8 Sol-#2/0 Str

1-1/2

2-40/50

1/2

3/4

1-1/8

QGFL29B1

#6 Str-250 kcmil

1-2/5

2-5/8

1/2

1/4

1-3/8

QGFL29B1T6

#6 Str-250 kcmil

1-5/8

3-1/8

1/2

3/4

1-3/8

QGFL31B1

2 AWG-350 kcmil

1-3/4

2-7/8

1/2

1/4

1-5/8

QGFL31B1T6

2 AWG-350 kcmil

1-3/4

3-1/4

1/2

3/4

1-5/8

QGFL34B1

1/0 -500 kcmil

2

3-1/8

1/2

1/4

1-3/4

QGFL34B1T6

1/0 -500 kcmil

2

3-5/8

1/2

3/4

1-3/4

QGFL39B1

350 kcmil-750 kcmil

2-1/4

3-1/4

1/2

1/4

1-3/4

QGFL39B1T6

350 kcmil-750 kcmil

2-1/4

3-5/8

1/2

3/4

1-3/4

QGFL44B1

750 kcmil-1000 kcmil

2-1/4

3-3/8

1/2

1/4

2-1/8

QGFL44B1T6

750 kcmil-1000 kcmil

2-1/4

4-1/8

1/2

3/4

2-1/8

QGFL46B1

1000 kcmil-1500 kcmil

2-1/4

4

1/2

1/4

2-1/2

QGFL46B1T6

1000 kcmil-1500 kcmil

2-1/4

4-1/2

1/2

3/4

2-1/2

QGFL48B1

1500 kcmil-2000 kcmil

2-1/4

4-3/4

1/2

1/4

3

L-21

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE FCB

TRANSFORMER TAP ADAPTERS

For Use On  Copper And 

Aluminum

Cast in one piece from copper alloy. Transformer 

tap  adapter  designed  to  accommodate  from  1 

to  6  NEMA  drilled  copper  or  aluminum  terminal 

taps from a single secondary transformer outlet. 

Tin-plated.  Order  mounting  hardware  and  tap 

terminals separately.

Material:  Copper

Notes : 

•  Plated versions: add the required suffix 

    to the catalog number. -TN for regular 

    tin plating

•  Please contact factory for other sizes, 

    combinations and availability

Substation

Transformer Tap Adapter | 230kV

TYPE E-C-G

TAP ADAPTERS

For Use On Copper Cable

Multi-tap, range-taking cast copper alloy connector 

designed to take 2, 3 or 4 conductors from a single 

secondary transformer outlet.

Material:  Copper Alloy

Notes : 

•  Plated versions: add the required suffix 

    to the catalog number. -TN for regular 

    tin plating

•  Please contact factory for other sizes, 

    combinations and availability

Catalog 

Number

Number of 

Conductors

Conductor 

Size

Dia.

H

J

L

W

E2C34G1

2

1/0 -500 

kcmil

0.78

3.88

1/2

6.25

3.50

E3C34G1

3

5.25

E4C34G1

4

6.88

L-22

Catalog 

Number

Fig. 

No.

Diameter

Ref.

L

P

FCB63-4N

1

0.50

5.25

3.75

2.25

FCB63-6N

2

0.50

5.25

5.50

2.25

FCB64-4N

1

0.75

5.75

4.00

2.75

FCB64-6N

2

0.75

5.75

5.75

2.75

FCB65-4N

1

1.00

7.00

4.25

4.00

FCB63-2NP300

Not Shown

0.50

5.00

3.50

3.00

FCB64-44NP50

Not Shown

0.75

9.00

5.00

5.00

NOTE:

 All pads are NEMA drilled.

Fig. 1

Fig. 2

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE HFBW

BAR CLAMPS

For Use On Copper Bar

The  clamp  assembly  eliminates  the  need  for 

drilling the flat bar and may be used in either indoor 

and outdoor applications. The open web design 

provides  a  uniform  clamping  pressure  while 

minimizing the weight of the connector.

Material:  Copper Alloy

Notes : 

•  Please contact factory for other sizes, 

    combinations and availability.

Substation

Bar Clamp | 230kV

Catalog Number

A

AA

J Dia.

L

W

HFB44G30W

4.00

4.00

1/2

5.75

5.75

HFB44G31W

4.00

4.00

1/2

5.75

5.75

HFB44G32W

4.00

4.00

1/2

5.75

5.75

L-23

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE HFB-P1

BAR CLAMP ASSEMBLY 
COMPONENTS

For Use On Copper Bar

To build your own high strength clamp assembly 

for multiple flat bar using type HFB-P1 bar clamps 

and clamping hardware, the following tables have 

been provided. The clamp assembly eliminates the 

need for drilling the flat bar and may be used in 

either indoor and outdoor applications. Hardware 

not included.

Material:  Copper Alloy

Notes : 

•  Please contact factory for other sizes, 

    combinations and availability

Substation

Bar Clamp | 230kV

Catalog Number

A

AA

J Dia.

L

HFB22P1

2.00

2.00

3/8

4.38

HFB33P1

3.00

3.00

3/8

4.38

HFB42P1

4.00

2.00

3/8

5.75

HFB44P1

4.00

4.00

1/2

5.75

HFB52P1

5.00

2.00

1/2

6.75

HFB53P1

5.00

3.00

1/2

6.75

HFB54P1

5.00

4.00

1/2

6.75

HFB55P1

5.00

5.00

5/8

7.13

HFB62P1

6.00

2.00

1/2

7.75

HFB63P1

6.00

3.00

1/2

7.75

HFB64P1

6.00

4.00

1/2

7.75

TYPE HFB-N

BAR CLAMP TAP PAD ADAPTERS

For Use On Copper Bar

High conductivity copper, tap pad adapter provides 

a NEMA drilled contact pad when assembled to the 

HFB-P1 clamps. Tap connections can be made 

from copper bus bar(s) without drilling, by bolting 

standard  mechanical  or  compression  terminal 

pads directly to the pre-drilled tap pad adapter.

Material:  Copper

Notes : 

•  Please contact factory for other sizes, 

    combinations and availability

Catalog Number

A

C

L

N

HFB33-4N

3.00

3.00

7.00

0.62

HFB44-4N

4.00

4.00

9.12

1.12

HFB66-6N

6.00

6.00

11.31

1.12

L-24

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE NNT

T-CONNECTOR

For Aluminum and Copper 

Tube to Tube

Aluminum alloy T-Connector for tubing run and tap. 

Properly  proportioned  to  permit  use  on  copper-

aluminum  conductor  combinations.  Captured 

hex  head  bolts  permit  one-wrench  installation. 

PENETROX™  joint  compound  recommended  on 

contact surfaces.

Material:  Aluminum Alloy

Hardware: Aluminum Hardware

Notes : 

•  PENETROX™ A joint compound is 

    recommended on contact surfaces

•  Please contact factory for other sizes, 

    combinations and availability

•  One-wrench installation.

Substation

 

Aluminum T Connector

Catalog 

Number

A - Run 

tube

AA - Tap 

tube 

B

J

Dia.

BB

NNT15A15A

1 IPS 

1 IPS 

3.50

1/2

3.50

6.81

3.38

NNT16A16A

1 1/4 IPS 

1 1/4 IPS 

3.75

1/2

3.75

7.44

3.38

NNT17A17A

1 1/2 IPS 

1 1/2 IPS 

4.00

1/2

4.00

7.88

3.88

NNT18A18A

2 IPS 

2 IPS 

4.25

5/8

4.25

9.06

4.44

NNT19A19A

2 1/2 IPS 

2 1/2 IPS 

4.50

5/8

4.50

9.38

4.94

NNT20A20A

3 IPS 

3 IPS 

5.00

5/8

5.00

10.94

5.44

NNT21A20A

3 1/2 IPS 

3 IPS 

5.50

5/8

5.00

11.06

5.56

NNT22A22A

4 IPS 

4 IPS 

6.00

5/8

6.00

12.63

6.19

L-25

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE NNTR

T-CONNECTOR

For Use On CABLE TO CABLE

Aluminum alloy T-Connector for a range of cable 

run to range of cable tap. One-wrench installation. 

   Material:  Aluminum Alloy

Hardware:  Aluminum Hardware

Notes : 

•  PENETROX™ A joint compound is 

recommended on contact surfaces

•  Please contact factory for other sizes, 

combinations and availability

•  One-wrench installation.

Substation

Aluminum T Connector

Catalog 

Number

A - Run Al 

Cable

A - Run ACSR Cable

AA - Tap 

Al Cable

AA - Tap ACSR Cable

B

J

Dia.

BB 

NNTR29A29A

1/0 AWG-

250 kcmil

1/0 (6/1) Raven AWG-

4/0 (6/1) Penquin AWG

1/0 AWG-

250 kcmil

1/0 (6/1) Raven AWG-

4/0 (6/1) Penquin AWG

2.75

1/2

2.75

5.56

2.56

2.50

NNTR32A25A

250 kcmil-

400 kcmil

4/0 (6/1) Penquin AWG-

397.5 (18/1) Chickadee 

kcmil

4 AWG-

1/0 AWG

4 (6/1) Swan AWG-

1/0 (6/1) Raven AWG

1.88

1/2

1.88

4.81

2.56

2.28

NNTR32A32A

250 kcmil-

400 kcmil

4/0 (6/1) Penquin AWG-

397.5 (18/1) Chickadee 

kcmil

250 kcmil-

400 kcmil

4/0 (6/1) Penquin AWG-

397.5 (18/1) Chickadee 

kcmil

3.00

1/2

3.00

5.94

2.56

2.63

NNTR36A29A

350 kcmil-

600 kcmil

336.4 (18/1) Merlin kcmil-

477.0 (18/1) Pelican kcmil

1/0 AWG-

250 kcmil

1/0 (6/1) Raven AWG-

4/0 (6/1) Penquin AWG

3.25

1/2

2.75

5.31

2.56

2.50

NNTR36A36A

350 kcmil-

600 kcmil

336.4 (18/1) Merlin kcmil-

477.0 (18/1) Pelican kcmil

350 kcmil-

600 kcmil

336.4 (18/1) Merlin kcmil-

477.0 (18/1) Pelican kcmil

3.25

1/2

3.25

6.31

2.56

2.75

NNTR42A32A

600 kcmil-

900 kcmil

477.0 (18/1) Pelican kcmil-

795 (54/7) Condor kcmil

250 kcmil-

400 kcmil

4/0 (6/1) Penquin AWG-

397.5 (18/1) Chickadee 

kcmil

3.50

1/2

3.00

6.38

3.13

2.63

NNTR42A36A

600 kcmil-

900 kcmil

477.0 (18/1) Pelican kcmil-

795 (54/7) Condor kcmil

350 kcmil-

600 kcmil

336.4 (18/1) Merlin kcmil-

477.0 (18/1) Pelican kcmil

3.50

1/2

3.25

6.63

3.13

2.75

NNTR42A42A

600 kcmil-

900 kcmil

477.0 (18/1) Pelican kcmil-

795 (54/7) Condor kcmil

600 kcmil-

900 kcmil

477.0 (18/1) Pelican kcmil-

795 (54/7) Condor kcmil

3.50

1/2

3.50

6.88

3.13

3.00

NNTR45A45A

900 kcmil-

1250 kcmil

715.5 (54/7) Crow kcmil-

1113 (54/19) Finch kcmil

900 kcmil-

1250 kcmil

715.5 (54/7) Crow kcmil-

1113 (54/19) Finch kcmil

3.75

1/2

3.75

7.31

3.25

3.19

NNTR46A42A

1250 kcmil-

1600 kcmil

1113 (54/19) Finch kcmil-

1431 (54/19) Plover kcmil

600 kcmil-

900 kcmil

477.0 (18/1) Pelican kcmil-

795 (54/7) Condor kcmil

3.75

1/2

3.50

7.25

3.44

3.00

NNTR46A46A

1250 kcmil-

1600 kcmil

1113 (54/19) Finch kcmil-

1431 (54/19) Plover kcmil

1250 kcmil-

1600 kcmil

1113 (54/19) Finch kcmil-

1431 (54/19) Plover kcmil

4.38

5/8

4.38

8.31

3.69

3.75

NNTR48A48A

1500 kcmil-

2000 kcmil

1272 (54/19) Pheasant 

kcmil-

1780 (54/19) kcmil

1500 kcmil-

2000 kcmil

1272 (54/19) Pheasant 

kcmil-

1780 (54/19) kcmil

4.50

5/8

4.50

8.63

3.81

3.88

L-26

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE NNTR

T-CONNECTOR

For Use On TUBE TO CABLE

Aluminum alloy T-Connector for tube run, range 

of cable tap. Properly proportioned to permit use 

on  copper-aluminum  combinations.  One-wrench 

installation.  PENETROX™  joint  compound 

recommended on contact surfaces.

Material:  Aluminum Alloy

Hardware:  Aluminum Hardware

Notes : 

•  PENETROX™ A joint compound is 

recommended on contact surfaces

•  Please contact factory for other sizes, 

combinations and availability

•  One-wrench installation.

Substation

Aluminum T Connector

Catalog 

Number

A - Run 

Al Pipe 

AA - Tap 

Al Cable

AA - Tap ACSR Cable

B

J

Dia.

BB

L

H

JJ

Dia.

W

NNTR14A29A

3/4 IPS 

1/0 AWG-

250 kcmil

1/0 (6/1) Raven AWG-

4/0 (6/1) Penquin AWG

3.25

1/2

2.75

5.81

3.06

0.50

2.50

NNTR15A36A

1 IPS 

350 kcmil-

600 kcmil

336.4 (18/1) Merlin kcmil-

477.0 (18/1) Pelican kcmil

3.50

1/2

3.25

6.56

3.31

0.50

2.75

NNTR15A42A

1 IPS 

600 kcmil-

900 kcmil

477.0 (18/1) Pelican kcmil-

795 (54/7) Condor kcmil

3.50

1/2

3.50

6.81

3.31

0.50

3.00

NNTR16A29A

1 1/4 IPS 

1/0 AWG-

250 kcmil

1/0 (6/1) Raven AWG-

4/0 (6/1) Penquin AWG

3.75

1/2

2.75

6.44

3.31

0.50

2.50

NNTR16A32A

1 1/4 IPS 

250 kcmil-

400 kcmil

4/0 (6/1) Penquin AWG-

397.5 (18/1) Chickadee kcmil

3.75

1/2

3.12

6.69

3.31

0.50

2.63

NNTR16A42A

1 1/4 IPS 

600 kcmil-

900 kcmil

477.0 (18/1) Pelican kcmil-

795 (54/7) Condor kcmil

3.75

1/2

3.50

7.19

3.31

0.50

3.00

NNTR17A29A

1 1/2 IPS 

1/0 AWG-

250 kcmil

1/0 (6/1) Raven AWG-

4/0 (6/1) Penquin AWG

4.00

1/2

2.75

6.69

3.81

0.50

2.50

NNTR18A29A

2 IPS 

4.00

1/2

2.75

7.56

4.44

0.50

2.50

NNTR19A42A

2 1/2 IPS 

600 kcmil-

900 kcmil

477.0 (18/1) Pelican kcmil-

795 (54/7) Condor kcmil

4.00

5/8

3.50

8.88

5.00

0.63

3.00

NNTR20A32A

3 IPS 

250 kcmil-

400 kcmil

4/0 (6/1) Penquin AWG-

397.5 (18/1) Chickadee kcmil

4.00

1/2

3.00

9.00

5.44

0.50

2.63

NNTR22A46A

4 IPS 

1250 kcmil-

1600 kcmil

1113 (54/19) Finch kcmil-

1431 (54/19) Plover kcmil

6.00

5/8

4.38

11.25

6.19

0.63

3.75

L-27

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE NS-A

COUPLER

For Use On Aluminum Tube To 

Tube

Aluminum alloy coupler for joining equal sizes of 

tube end to end. Properly proportioned to permit 

use on aluminum-copper conductor combinations. 

One-wrench  installation.  PENETROX™  joint 

compound recommended on contact surfaces.

Material:  Aluminum Alloy

Hardware:  Aluminum Hardware

Notes : 

•  PENETROX™ A joint compound is 

    recommended on contact surfaces

•  Please contact factory for other sizes, 

    combinations and availability

Substation

Aluminum Bolted Coupler

Catalog 

Number

A -  tube 

J

Dia.

NS14A14A

3/4 IPS 

1/2

6.75

2.06

2.80

NS15A15A

1 IPS 

7.25

2.18

3.06

NS16A16A

1 1/4 IPS 

7.75

3.50

3.41

NS17A17A

1 1/2 IPS 

8.25

4.00

3.64

NS18A18A

2 IPS 

5/8

8.75

4.62

4.50

NS19A19A

2 1/2 IPS 

9.31

4.26

5.00

NS20A20A

3 IPS 

10.25

5.62

5.63

NS21A21A

3 1/2 IPS 

8.00

5.25

6.14

NS22A22A

4 IPS 

12.00

5.94

6.62

NS23A23A

4 1/2 IPS 

13.25

6.38

7.14

NS24A24A

5 IPS 

14.38

6.94

7.70

NS86A86A

6 IPS 

16.25

8.04

8.76

TYPE NA-A

TERMINAL

For Use On Tube To Flat

Aluminum alloy terminal for joining copper or 

aluminum tube to copper or aluminum pad. 

Material:  Aluminum Alloy

Hardware:  Aluminum Hardware

Notes : 

•  Properly proportioned to minimize 

    conductor corrosion due to galvanic 

    action. When properly used, this 

    item does not require use of 

    bimetallic plates. Please ask 

    BURNDY

®

 Technical Support for 

    recommendations

•  PENETROX™ A joint compound is 

    recommended on contact surfaces

•  Please contact factory for other sizes, 

    combinations and availability

•  One wrench installation

Catalog 

Number

Al tube

Dia.

H

NA15A-2N

1 IPS 

3.50

1.88

1/2

6.75

3.38

0.38

3.06

NA15A-4N

3.50

3.00

1/2

6.75

3.38

0.38

3.06

NA16A-2N

1 1/4 IPS 

3.75

2.25

1/2

7.00

3.38

0.44

3.40

NA17A-2N

1 1/2 IPS 

4.00

2.50

1/2

7.50

3.88

0.50

3.64

NA17A-4N

4.00

3.00

1/2

7.50

3.88

0.50

3.64

NA18A-2N

2 IPS 

4.25

2.75

5/8

7.50

4.47

0.50

4.50

NA18A-4N

4.25

3.12

5/8

7.50

4.47

0.50

4.50

NA19A-4N

2 1/2 IPS

4.50

3.75

5/8

7.75

4.97

0.69

5.00

NA20A-4N

3 IPS

5.00

4.38

5/8

8.31

5.47

0.69

5.62

NA22A-4N

4 IPS

6.00

5.25

5/8

9.31

6.22

0.81

6.62

L-28

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE XA-A

EXPANSION TERMINAL

For Use On Expansion Tube To Flat

Aluminum  alloy  expansion  connector  for  joining 

tube to copper or aluminum bar or equipment pads. 

Flexible aluminum straps allow for  longitudinal or 

lateral movement and carries full current load of the 

joint. PENETROX™ joint compound recommended 

on  contact  surfaces.  Pad  contact  surface  is  on 

centerline of conductor.

Material:  Aluminum Alloy

Hardware:  Aluminum Hardware

Notes : 

•  PENETROX™ A joint compound is 

    recommended on contact surfaces

•  One side of pad finished on centerline 

    of tubing. For finished pads on both 

    sides add suffix “-Q” to catalog number.

Substation

Aluminum Bolted Terminal l 230kV

Catalog 

Number *

Fig. #

Al tube 

Schd 40

C

J

Dia.

H

XA15A-4N

2

1 IPS

3.00

1/2

13.19

3.70

0.38

3.06

XA16A-4N

2

1 1/4 IPS

3.00

1/2

13.62

4.00

0.44

3.41

XA18A-4N

2

2 IPS

3.12

5/8

15.50

5.26

0.50

4.50

XA19A-4N

2

2 1/2 IPS

3.75

5/8

16.94

5.72

0.69

5.00

XA20A-4N

2

3 IPS

4.38

5/8

18.52

6.80

0.69

5.62

XA21A-4N

2

3 1/2 IPS

4.75

5/8

20.00

7.60

0.81

6.12

XA22A-4N

2

4 IPS

5.25

5/8

21.00

8.16

0.81

6.62

XA24A-4N

2

5 IPS

6.50

5/8

24.15

9.74

0.81

7.69

*  Conforms to 4-hole NEMA mounting standards.

L-29

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE NAR

TERMINAL

For Use On Cable To Pad

Aluminum  alloy  bolted  type  terminal  for  joining 

aluminum  cable  to  copper  or  aluminum  pads. 

Drilling  in  pad  conforms  to  NEMA  Standards. 

PENETROX™ joint compound recommended on 

contact surfaces.

Material:  Aluminum Alloy

Hardware:  Aluminum Hardware

Notes : 

•  Properly proportioned to minimize 

    conductor corrosion due to galvanic 

    action. When properly used, this item 

    does not require use of bimetallic plates. 

    Please ask BURNDY

®

 Technical 

    Support for recommendations.

•  PENETROX™ A joint compound is 

    recommended on contact surfaces.

•  Please contact factory for other sizes, 

    combinations and availability.

•  One-wrench installation. 

Substation

Aluminum Bolted Terminal l 230kV

Catalog 

Number

Fig. # Aluminum Stranded

Aluminum ACSR

B

J

Dia.

L

T

W

NAR25A2N

1

4 AWG-1/0 AWG

4 (6/1) Swan AWG-

1/0 (6/1) Raven AWG

2.00

1/2

5.10

2.72

1.25

0.31

2.28

NAR29A2N

2

1/0 AWG-250 kcmil

1/0 (6/1) Raven AWG-

4/0 (6/1) Penquin AWG

2.75

1/2

6.06

2.75

1.38

0.31

2.50

NAR29A4N

2

2.88

1/2

6.06

2.75

3.00

0.31

3.00

NAR32A2N

2

250 kcmil-400 kcmil

4/0 (6/1) Penquin AWG-

397.5 (30/7) Larkspur kcmil

3.00

1/2

6.31

2.88

1.63

0.38

2.63

NAR32A4N

2

4/0 (6/1) Penquin AWG-

397.5 (30/7) Larkspur kcmil

3.00

1/2

6.31

2.88

3.00

0.38

3.00

NAR36A2N

2

350 kcmil-600 kcmil

336.4 (30/7) Oriole kcmil-

477. (30/7) Hen kcmil

3.25

1/2

6.63

2.81

1.69

0.38

2.75

NAR36A4N

2

336.4 (30/7) Oriole kcmil-

477. (30/7) Hen kcmil

3.25

1/2

6.63

2.81

3.00

0.38

3.00

NAR42A2N

1

600 kcmil-900 kcmil

477. (30/7) Hen kcmil-

795 (30/19) Mallard kcmil

3.50

1/2

6.81

3.31

2.00

0.50

3.00

NAR42A4N

2

3.50

1/2

6.81

3.31

3.00

0.50

3.00

NAR45A2N

1

900 kcmil-1250 kcmil

715.5 (30/19) Redwing kcmil-

1113 (54/19) Finch kcmil

2.63

1/2

7.12

3.31

2.63

0.50

3.20

NAR45A4N

2

3.75

1/2

7.12

3.31

3.00

0.50

3.20

NAR46A2N

1

1250 kcmil-1600 kcmil

1113 (54/19) Finch kcmil-

1431 (54/19) Plover kcmil

4.38

5/8

7.69

3.69

2.75

0.56

3.75

NAR46A4N

2

4.38

5/8

7.69

3.69

3.00

0.56

3.75

NAR48A2N

1

1500 kcmil-2000 kcmil 1272 (54/19) Pheasant kcmil-

1780 (54/19) kcmil

4.50

5/8

7.88

3.94

2.75

0.69

3.88

NAR48A4N

2

4.50

5/8

7.88

3.94

3.00

0.69

3.88

L-30

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE NBC-A

BOLTED CONNECTOR

For Use On Pipe To Centerline Tap 

Pad

Aluminum  alloy  bolted  type  terminal  for  joining 

aluminum  tube  to  copper  or  aluminum  pads. 

Drilling  in  pad  conforms  to  NEMA  Standards. 

PENETROX™ joint compound recommended on 

contact surfaces.

Material:  Aluminum Alloy

Hardware:  Aluminum Hardware

Notes : 

•  Properly proportioned to minimize 

    conductor corrosion due to galvanic 

    action. When properly used, this 

    item does not require use of 

    bimetallic plates. Please ask 

    BURNDY

®

 Technical Support for 

    recommendations

•  PENETROX™ A joint compound is 

    recommended on contact surfaces

•  Please contact factory for other sizes, 

    combinations and availability

•  One-wrench installation.

Substation

Aluminum T Connector

Catalog 

Number

Fig. #

Al tube

J

Dia.

L

NBC14A2N

1

3/4 IPS 

3.25

1/2

6.56

3.50

3/8

NBC15A-2N

1

1 IPS 

3.50

1/2

6.81

3.00

3/8

NBC15A34N

2

3.50

1/2

6.81

3.00

3/8

NBC16A2N

1

1 1/4 IPS 

3.75

1/2

7.15

3.25

3/8

NBC16A34N

2

3.75

1/2

7.15

3.25

3/8

NBC16A44N

3

3.75

1/2

8.15

3.25

3/8

NBC17A2N

1

1 1/2 IPS 

4.00

1/2

7.39

3.50

3/8

NBC17A34N

2

4.00

1/2

7.39

3.50

3/8

NBC17A44N

3

4.00

1/2

8.39

3.50

3/8

NBC18A2N

1

2 IPS 

4.25

5/8

8.25

4.00

3/8

NBC18A34N

2

4.25

5/8

8.25

4.00

3/8

NBC18A-44N

3

4.25

5/8

9.25

4.00

3/8

NBC19A34N

2

2 1/2 IPS 

4.50

5/8

8.75

4.50

1/2

NBC19A44N

3

4.50

5/8

9.75

4.50

1/2

NBC20A2N

1

3 IPS 

5.00

5/8

9.37

4.50

1/2

NBC20A34N

2

5.00

5/8

9.37

4.50

1/2

NBC20A-44N

3

5.00

5/8

10.37

4.50

1/2

NBC21A44N

3

3 1/2 IPS 

5.50

5/8

10.89

5.00

5/8

NBC22A2N

1

4 IPS 

6.00

5/8

10.38

5.50

5/8

NBC22A34N

2

6.00

5/8

10.37

5.50

5/8

NBC22A44N

3

6.00

5/8

11.37

5.50

5/8

NBC24A2N

1

5 IPS 

7.00

5/8

12.45

6.00

5/8

NBC24A34N

2

7.00

5/8

12.45

6.00

5/8

NBC24A44N

3

7.00

5/8

13.45

6.00

5/8

NBC86A44N

3

6 IPS 

8.00

5/8

13.51

7.25

3/4

L-31

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE UHG

BUS SUPPORT

For Use On Fixed Or Rigid Pipe To 

Base

Aluminum alloy bus support for mounting tube on 

post or pedestal insulators. Properly proportioned to 

minimize conductor corrosion due to galvanic action. 

Caps are reversible for FIX or RIGID fit. One-wrench 

installation.Supplied with hardware for mounting to 

cap of insulator. 

Material:  Aluminum Alloy

Hardware:  Aluminum Hardware

Notes : 

•  PENETROX™ A joint compound is 

    recommended on contact surfaces.

•  Specify base mounting hardware, if 

    required, by adding suffix -B to catalog 

    number.

•  For static clips add “-CH” to Catalog 

    Number.

Substation

Aluminum Bus Support

Catalog Number

A

BC

G

L

H

W

UHG13A3CH

1/2 IPS 

3.00

1.75

7.44

3.09

2.66

UHG14A-3

3/4 IPS 

2.00

7.44

3.50

2.94

UHG14A3CH

3/4 IPS 

7.44

3.50

2.94

UHG15A-3

1 IPS 

7.44

3.88

3.06

UHG15A3CH

1 IPS 

7.44

3.88

3.19

UHG15A-5

1 IPS 

5.00

2.25

9.82

3.82

3.19

UHG15A5CH

1 IPS 

9.82

3.82

3.19

UHG16A3CH

1 1/4 IPS 

3.00

7.68

3.79

3.50

UHG16A5CH

1 1/4 IPS 

5.00

2.38

10.06

3.94

3.50

UHG17A-3

1 1/2 IPS 

3.00

2.50

7.68

4.06

3.66

UHG17A3CH

1 1/2 IPS 

7.68

4.06

3.66

UHG17A-5

1 1/2 IPS 

5.00

10.06

4.06

3.66

UHG17A5CH

1 1/2 IPS 

10.06

4.06

3.66

UHG18A-3

2 IPS 

3.00

2.75

7.68

5.25

4.12

UHG18A3CH

2 IPS 

7.68

5.25

4.12

UHG18A-5

2 IPS 

5.00

10.06

4.61

4.12

UHG18A5CH

2 IPS 

10.06

4.61

4.12

UHG19A-3

2 1/2 IPS 

3.00

3.12

7.68

5.23

4.62

UHG19A3CH

2 1/2 IPS 

7.68

5.23

4.62

UHG19A5CH

2 1/2 IPS 

5.00

10.56

5.23

4.62

UHG20A3CH

3 IPS 

3.00

3.62

9.25

6.09

5.62

UHG20A-5

3 IPS 

5.00

10.56

6.09

5.62

UHG20A5CH

3 IPS 

10.56

6.09

5.62

UHG20A7CH

3 IPS 

7.00

12.80

8.46

8.46

UHG21A-3

3 1/2 IPS 

3.00

4.00

8.18

6.74

6.16

UHG21A3CH

3 1/2 IPS 

8.18

6.74

6.16

UHG21A5CH

3 1/2 IPS 

5.00

10.56

6.74

6.16

UHG22A3CH

4 IPS 

3.00

4.50

8.18

7.50

6.62

UHG22A-5

4 IPS

5.00

11.34

7.50

6.62

UHG22A5CH

4 IPS 

11.34

7.50

6.62

UHG24A-3

5 IPS 

3.00

5.25

8.68

8.86

7.70

UHG24A3CH

5 IPS 

8.68

8.86

7.70

UHG24A-5

5 IPS 

5.00

11.56

8.86

7.70

UHG24A5CH

5 IPS 

11.56

8.86

7.70

UHG83A5

8 IPS 

7.16

11.56

11.84

10.12

UHG86A5CH

6 IPS 

5.56

11.56

9.94

8.75

L-32

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE UHKR-A

BUS SUPPORT

For Use On Cable Or Tube To Base

Aluminum alloy bus support for mounting a wide 

range of cable or tube on post or pedestal type 

insulators. Supplied with hardware for mounting to 

cap of insulator.

Material:  Aluminum Alloy

Hardware:  Aluminum Hardware

Notes : 

•  PENETROX™ A joint compound is 

    recommended on contact surfaces.

•  Specify base mounting hardware, if 

    required, by adding suffix -B to catalog 

    number.

•  Please contact factory for other sizes, 

   combinations and availability.

Substation

Aluminum Bus Support

Catalog 

Number

Tube 

Size

Al 

Cable

ACSR 

Cable

BC 

G *

UHKR11A3

1/4 IPS 

4 AWG-4/0 AWG

6 (6/1) Turkey AWG-

4/0 (6/1) Penquin AWG

3.00

1.16

7.56

2.63

UHKR11A5

1/4 IPS 

5.00

1.16

8.50

2.63

UHKR13A3

3/8 IPS -1/2 IPS 

250 kcmil-550 kcmil

266.8 (26/7) Owl kcmil-

477. (30/7) Hen kcmil

3.00

1.32

7.56

3.88

UHKR13A5

3/8 IPS -1/2 IPS 

5.00

1.32

8.88

2.88

UHKR14A3

3/4 IPS 

600 kcmil-1113 kcmil

556.5 (26/7) Dove kcmil-

1033.5 (54/7) Curlew kcmil

3.00

1.72

7.56

3.56

UHKR14A5

3/4 IPS 

5.00

1.53

9.06

3.38

UHKR16A3

1 IPS -1 1/4 IPS 

1000 kcmil-2000 kcmil

1113 (54/19) Finch kcmil-

1780 (84/19) Chukar kcmil

3.00

1.97

7.56

4.06

UHKR16A5

1 IPS -1 1/4 IPS 

5.00

1.80

9.25

3.88

UHKR17A3

1 1/4 IPS -1 1/2 IPS 

2000 kcmil-2500 kcmil

1780 (84/19) Chukar kcmil-

2156 (84/19) Bluebird kcmil

3.00

2.50

8.02

4.62

UHKR17A5

1 1/4 IPS -1 1/2 IPS 

5.00

2.50

9.31

4.62

*   With maximum conductor in place.

L-33

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE LB-A

END CAP

For Use On Pipe End Cap

Aluminum alloy end cap for aluminum tube. Driven 

into  place  for  a  secure  fit.  Seals  out  moisture, 

reduces electrostatic loss and eliminates hazards 

created by nesting birds.

Material:  Aluminum Alloy

Hardware:  Aluminum Hardware

Notes : 

•  Installation instructions available upon 

    request.

•  Please contact factory for other sizes, 

   combinations and availability.

Substation

Aluminum End Cap

Catalog Number

Al tube 

Sch 40

Al tube 

Sch 80

LB13A

1/2 IPS 

N/A

0.38

1.25

LB14A

3/4 IPS 

0.50

1.37

LB15A

1 IPS 

1.35

LB16A

1 1/4 IPS 

1.35

LB17A

1 1/2 IPS 

1.35

LB18A

2 IPS 

0.88

2.16

LB19A

2 1/2 IPS 

2.24

LB20A

3 IPS 

2.29

LB21A

3 1/2 IPS 

2.33

LB22A

4 IPS 

2.22

LB23A

4 1/2 IPS 

2.28

LB24A

5 IPS 

2.45

LB83A

8 OD 

0.75

2.28

LB86A

6 IPS 

0.88

2.57

LB88A

8 IPS 

0.75

2.28

LB53A

N/A

1/2 IPS 

0.38

1.25

LB54A

N/A

3/4 IPS 

0.50

1.37

LB55A

N/A

1 IPS 

1.35

LB56A

N/A

1 1/4 IPS 

1.35

LB57A

N/A

1 1/2 IPS 

1.35

LB58A

N/A

2 IPS 

0.88

2.16

LB59A

N/A

2 1/2 IPS 

2.24

LB90A

N/A

3 IPS 

0.88

2.29

LB91A

N/A

3 1/2 IPS 

2.33

LB92A

N/A

4 IPS 

2.22

LB94A

N/A

5 IPS 

2.45

LB96A

N/A

6 IPS 

2.57

L-34

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE WAS-A

WELDMENT TERMINAL 
CONNECTOR

For Use On Tube To Pad

Aluminum  alloy  weld  type  terminal  for  joining 

aluminum  tube  to  copper  or  aluminum  pads. 

Drilling  in  pad  conforms  to  NEMA  standards. 

PENETROX™ joint compound recommended on  

pad contact surfaces.

Material:  Aluminum Alloy

Notes : 

•  Welding to be done by customer

•  Before welding scratch brush connector 

    and conductor contact surface dry, then 

    apply an oxide inhibitor.

•  Tongue finished on one side only. For 

    tongue finished on both sides, add suffix 

    “-Q” to catalog number.

Substation

Aluminum Welded Terminal

Catalog Number

Fig. 

#

Al 

Pipe

C

H

WAS14A-2N

1

3/4 IPS 

2.50

2.00

6.50

1.34

19/50

WAS15A-2N

1

1 IPS 

2.75

2.00

6.75

1.80

19/50

WAS15A-34N

2

2.75

3.00

6.75

1.80

19/50

WAS16A-2N

1

1 1/4 IPS 

3.00

2.00

7.00

2.15

19/50

WAS16A34N

2

3.00

3.00

7.00

2.15

19/50

WAS17A-2N

1

1 1/2 IPS 

3.25

2.00

7.25

2.38

11/25

WAS17A-34N

2

3.25

3.00

7.25

2.38

19/50

WAS18A-2N

1

2 IPS 

3.50

2.00

7.50

2.84

11/25

WAS18A-34N

2

3.50

3.00

8.62

2.84

19/50

WAS18A44N

3

3.63

4.00

8.62

2.84

1/2

WAS19A-2N

1

2 1/2 IPS 

3.63

2.00

7.87

3.32

14/25

WAS19A-34N

2

3.63

3.00

8.87

3.32

1/2

WAS19A-44N

3

3.63

4.00

8.87

3.32

1/2

WAS20A-2N

1

3 IPS 

3.67

2.00

8.25

3.98

5/8

WAS20A-34N

2

3.75

3.00

8.25

3.98

31/50

WAS20A-44N

3

3.75

4.00

9.25

3.98

5/8

WAS21A34N

2

3 1/2 IPS 

4.25

3.00

8.38

4.51

31/50

WAS22A34N

2

4 IPS 

4.25

3.00

8.38

5.01

3/4

WAS22A-44N

3

4.25

4.00

9.38

5.01

3/4

L-35

section l-substation_bolted-html.html
background image

BURNDY

®

US: 1-800-346-4175 

 

www.burndy.com     

         Canada: 1-800-387-6487

TYPE WASC-A-N

CENTREFORMED WELDEMENT 
TERMINAL

For Use On Tube To Pad

Aluminum alloy weldment terminal. Type WASC-

A-N has one contact surface on the center line of 

the tube. Holes are NEMA spaced for terminating 

aluminum or copper mating pads. PENETROX™ 

joint compound recommended for use on contact 

surfaces.

Material:  Aluminum Alloy

Notes : 

•  Welding to be done by customer

•  Before welding scratch brush connector 

    and conductor contact surface dry, then 

    apply an oxide inhibitor.

•  Tongue finished on one side only. For 

    tongue finished on both sides, add suffix 

    “-Q” to catalog number.

Substation

Aluminum Welded Terminal

Catalog 

Number

Fig. 

#

A-Al 

Pipe

L

H

T

WASC15A2N

1

1 IPS 

2.75

6.69

1.46

19/50

2.00

WASC16A34N

2

1 1/4 IPS 

3.00

7.00

1.86

19/50

3.00

WASC17A2N

1

1 1/2 IPS 

3.25

7.31

2.15

7/16

2.54

WASC17A34N

2

3.25

7.31

2.15

11/25

3.00

WASC18A2N

1

2 IPS 

3.50

7.56

2.62

1/2

3.03

WASC18A34N

2

3.50

7.56

2.62

1/2

3.03

WASC19A34N

2

2 1/2 IPS 

3.75

7.88

3.17

14/25

3.67

WASC19A44N

3

3.75

8.88

3.17

14/25

4.00

WASC20A2N

1

3 IPS 

4.00

8.13

3.79

31/50

4.29

WASC20A34N

2

4.00

8.13

3.79

31/50

4.29

WASC20A44N

3

4.00

9.13

3.79

31/50

4.29

WASC21A34N

2

3 1/2 IPS 

4.25

8.38

4.28

31/50

4.79

WASC21A44N

3

4.25

9.38

4.28

31/50

4.79

WASC22A34N

2

4 IPS 

4.25

8.38

4.78

3/4

5.29

WASC22A44N

3

4.25

9.38

4.78

3/4

5.29

WASC24A44N

3

5 IPS 

4.25

9.50

5.95

3/4

6.59

WASC24A66N

4.25

9.50

5.95

3/4

6.59

L-36

section l-substation_bolted-html.html
background image

BURNDY

®

Canada: 1-800-387-6487   

 

www.burndy.com     

      US: 1-800-346-4175

TYPE WG

GROUND STUD

For Use On Stud To Tube

Range-taking weldment stud for grounding aluminum 

tube.

Material:  Aluminum Alloy

Notes : 

•  Welding to be done by customer

•  Before welding scratch brush connector 

    and conductor contact surface dry, then 

    apply an oxide inhibitor.

•  Please contact factory for availability.

Substation

Aluminum Welded Ground Stud

Catalog Number

Al Pipe

B

Y

WG19A

1 IPS -2 1/2 IPS 

3

8.19

0.75

1.32

WG86A

3 IPS -6 IPS

2

10.31

0.75

3.06

L-37