Description
dimensions: 200 x 130 x 114.5 mm. Weight: 2.8 kg.
Power supplies, type Camtec HPV
Single-phase AC/DC power supply for rail mounting, V/I characteristic. Input voltage: 115/230 V. Input range AC: 90 to 132 V/184 to 265 V. Input range DC: 250 to 375 V. Backup time (230 VAC): 50 ms. Operating temperatures: -20 to +70C. Table index: type, output voltage, output current, residual ripple, efficiency.
Model | HPV04801 | |||
Power | 480W | |||
Nominal AC Input | 115/230Vac select | |||
Input Range AC | 90..115Vac/184..265Vac | |||
Input Range DC | 250… 375Vdc | |||
Input Frequency | 47… 63Hz | |||
Hold-Up Time | 40ms | |||
Inrush Current Protection | NTC <40A | |||
Autostart | Soft start 20ms | |||
Output Voltage | 72V | 110V | 150V | 240V |
Adjust Range Vout | 58… 86V | 86… 132V | 132… 180V | 180… 240V |
Ripple & Noise mVpp | 150mV | 200mV | 200mV | 300mV |
Nominal Output Current | 6,7A | 4,4A | 3,2A | 2,2A |
Power Boost <=60°C/60s | 7,2A | 5,3A | 3,8A | 2,6A |
Stability at Load Switch | ±0,5% | |||
Transient Time | < 1ms | |||
Efficiency | 93 % | |||
Basic load | Idling-proof | |||
Short Circuit Protection | Continuous | |||
Ambient Operation Temperature | -20°C… +70°C | |||
Cooling | Natural Convection | |||
Temperature Monitoring | Yes | |||
Dimensions (WxHxD) | 200x130x114,5mm | |||
IP-Range | IP20 | |||
Safety Norms | CSA UL CE according to IEC60950-1 | |||
Safety IEC | EN60950-1 EN50178 EN60204-1 | |||
Safety Class 1(A) | VDE0100 VDE0805 | |||
Input to Output Isolation | 3000Vac | |||
Climatic Class, Humidity | 3k3, 95% non condensing | |||
EMI | EN55022B | |||
EMS | EN61000-6-2,3 | |||
MTBF IEC61709 | 400000h | |||
Power Good Relay | Yes, Option | |||
Ordering options | Protective coating, Power Good Relay (PG) |
Manufacturer:Camtec
Datasheet:Camtec_HPV04801_E0613F.pdf